Part number for Fluke: FLK-1663 The Fluke 1663 Multifunction Tester (EVSE version), like other products in Fluke's multifunction tester line, can carry out a wide variety of tests and measurements to Fluke's customary high standards of accuracy and precision. Its mix of simple operation and sophisticated measurements makes it an especially helpful tool for field electricians. The Fluke 1663 performs continuity tests, RCD testing, ramp tests, and continuity tests in addition to taking measurements for True RMS AC voltage, insulation resistance, loop and line impedance, projected earth fault current, tripping speed, and RCD/FI tripping current.The Fluke 1663 offers versatility in addition to accuracy, dependability, and precision because the user has many options for resolution and range for the majority of the functions, as well as a variety of type options for RCD, RCD-FI tripping, and trip speed testing. Other capabilities of the Fluke 1663 enable the user to quickly, easily, and safely take advantage of the complex measuring options. First off, the device is operated by a straightforward dial interface, eliminating the need for complicated menus. Additionally, auto-testing for a number of functions means that just one connection and one button are required to perform some complex assessments, speeding up and simplifying measures. Additionally, simultaneous measurement decreases the chance of error and saves time, particularly because the self-test mechanism minimises manual testing. The Fluke 1663 can test the DC protection devices at EV charging stations utilising the RCD type B (smooth DC Currents) VAR mode when paired with an adaptor like the Fluke FEV300 (sold separately). The test currents for RCD type A-EV or RDC-DD acc can be tested with this generator in accordance with IEC 62955 safety regulations (6/60/200 mA and ramp <2 to 6 mA ramp). This enables quick and simple further testing of 6mA DC RCD monitors on charging points by the operator. The Fluke 1663 is classified as Cat III to 500V for overvoltage and complies with all relevant national requirements, giving it the safety credentials to go along with its superb measuring and practical capabilities. Additionally, dangerous earth voltages are automatically identified and warned to the user. Results are displayed on the device's clear LCD screen, which is portable, tough, and IP40-sealed. A sturdy travel bag, cushioned neck strap, test leads, a remote control probe, a fused test probe set, a mains cord, a zero adapter, a remote control probe, and a calibration certificate are included with the Fluke 1663 multifunction 17th edition tester.
- measurement of AC voltage:-
Range:500 volts
1V as the resolution
Accuracy from 45 to 66 Hz: 0.8% + 3 counts
360kΩ input impedance
660V rms overload protection
RLO continuity testing
Range (autoranging): 20 cents, 200 cents, and 2000 cents
Resolutions of 0.01Ω, 0.1Ω, and 1Ω
Voltage of an open circuit: >
- 4V
General:-
Size: 10 x 25 x 12.5 cm (L x W x H).
Weight (batteries included): 1.3 kg
IP-40 Sealing
Cat III to 500V
- Cat IV to 300V of excess voltage
Safety: Meets with the demands of EN61010-1 Ed 2.0 (2001-02), UL61010, ANSI/ISA -s82.02.01 2000, and CAN/CSA c22.2 No. 1010 2nd edition.
Performance: Second Editions of EN61557-1 to EN61557-7 and EN61557-10
6 x AA batteries
measuring insulation resistance:-
Test voltages: 50, 100, 250, 500, and 1000V
tTest voltage accuracy (at the specified test current): +10%, -0%
Ranges of insulation resistance: 20 to 50 MΩ, 20 to 100 MΩ, 20 to 200 MΩ, 20 to 200 MΩ, and 20 to 200 MΩ.
Resolution: 0.01MΩ / 0.1MΩ
- 0.01MΩ / 0.1MΩ
- 0.01MΩ / 0.1MΩ
- 0.01MΩ / 0.1MΩ / 1MΩ
- 0.01MΩ / 0.1MΩ / 1MΩ
Test currents of 1mA at 50kΩ
- 1mA at 100kΩ
- 1mA at 250kΩ
- 1mA at 500kΩ
- 1mA at 1MΩ
Impedance of loops and lines (ZI):-
High current mΩ mode
- range: 10Ω
- 0.001Ω
-
Resolutions of 0.01Ω, 0.1Ω, and 1Ω
PSC test for prospective earth fault current:-
1000A to 10kA (50kA) range
1A/0.1kA resolution
By dividing the actual mains voltage by the measured loop (L-PE) resistance or line (L-N) resistance, respectively, prospective earth fault current (PEFC) or prospective short current (PSC) are determined.
RCD testing and varieties of RCD testing:-
Type of RCD: A4, AC1, G2, S3
Notes: (1) Reacted to AC, (2) In general no delay, (3) Time delay, and (4) Reacted to pulsed signal
Measurement of RCD/FI-Tripping Current and Ramp Testing (IΔN):-
30% to 110% of the RCD-rated current is the current range.
10% of IΔN2 as a step size
Dwell time: Type G: 300 ms
- Type S: 500 ms
±5%5% accuracy in measurements
Trip current ranges that have been specified (EN 61008-1) are as follows: 50% to 100% for Type AC, 35% to 140% for Type A (>
- 10 mA), 35% to 200% for Type A (≤10 mA), 50% to 200% for Type B, and ²5% for Type B.
Notes: For Type A IΔN >
- 10 mA, ¹30% to 150%
- for Type A IΔN = 10 mA, 30% to 210%
- for Type B, 20% to 210%.
Testing the tripping speed (T):-
Current settings1: 10-30-100-300-500-1000mA - VAR
- 10-30-100mA
A multiplier of 0.5, 1, and 5
Measurement of AC voltage:-
Range:500 volts
1V as the resolution
Accuracy from 45 to 66 Hz: 0.8% + 3 counts
360kΩ input impedance
660V rms overload protection
RLO continuity testing
Range (autoranging): 20 cents, 200 cents, and 2000 cents
Resolutions of 0.01Ω, 0.1Ω, and 1Ω
Voltage of an open circuit: >
- 4V
Test for Earth Resistance (RE)
Range: 200Ω / 2000Ω
0.1 / 1 resolution
the frequency 128 Hz.
Voltage at output: 25V
Connect Fluke:-
Operating systems iOS 8 and later or Android 4.4 and later support Fluke Connect.
General:-
Size: 10 x 25 x 12.5 cm (L x W x H).
Weight (batteries included): 1.3 kg
IP-40 Sealing
Cat III to 500V
- Cat IV to 300V of excess voltage
Safety: Meets with the demands of EN61010-1 Ed 2.0 (2001-02), UL61010, ANSI/ISA -s82.02.01 2000, and CAN/CSA c22.2 No. 1010 2nd edition.
Performance: Second Editions of EN61557-1 to EN61557-7 and EN61557-10
6 x AA batteries
Measuring insulation resistance:-
Test voltages: 50, 100, 250, 500, and 1000V
tTest voltage accuracy (at the specified test current): +10%, -0%
Ranges of insulation resistance: 20 to 50 MΩ, 20 to 100 MΩ, 20 to 200 MΩ, 20 to 200 MΩ, and 20 to 200 MΩ.
Resolution: 0.01MΩ / 0.1MΩ
- 0.01MΩ / 0.1MΩ
- 0.01MΩ / 0.1MΩ
- 0.01MΩ / 0.1MΩ / 1MΩ
- 0.01MΩ / 0.1MΩ / 1MΩ
Test currents of 1mA at 50kΩ
- 1mA at 100kΩ
- 1mA at 250kΩ
- 1mA at 500kΩ
- 1mA at 1MΩ
Impedance of loops and lines (ZI):-
High current mΩ mode
- range: 10Ω
- 0.001Ω
-
Resolutions of 0.01Ω, 0.1Ω, and 1Ω
PSC test for prospective earth fault current:-
1000A to 10kA (50kA) range
1A/0.1kA resolution
By dividing the actual mains voltage by the measured loop (L-PE) resistance or line (L-N) resistance, respectively, prospective earth fault current (PEFC) or prospective short current (PSC) are determined.
RCD testing and varieties of RCD testing:-
RCD type: G2, S3, AC1,
Model 1664: A, AC, B5, S
Notes: (1) Reacted to AC, (2) In general no delay, (3) Time delay, and (4) Reacted to pulsed signal
- (5) Responds to smooth DC signal.
Measurement of RCD/FI-Tripping Current and Ramp Testing (IΔN):-
30% to 110% of the RCD-rated current is the current range.
10% of IΔN2 as a step size
Dwell time: Type G: 300 ms
- Type S: 500 ms
±5%5% accuracy in measurements
Trip current ranges that have been specified (EN 61008-1) are as follows: 50% to 100% for Type AC, 35% to 140% for Type A (>
- 10 mA), 35% to 200% for Type A (≤10 mA), 50% to 200% for Type B, and ²5% for Type B.
Notes: For Type A IΔN >
- 10 mA, ¹30% to 150%
- for Type A IΔN = 10 mA, 30% to 210%
- for Type B, 20% to 210%.
Testing the tripping speed (T):-
Current settings1: 10-30-100-300-500-1000mA - VAR
- 10-30-100mA
A multiplier of 0.5, 1, and 5
Notes: Only type AC supports 1000mA, type A can only handle 700mA in VAR mode, and type B is not supported by VAR mode.
- Testing RCD and loops on auto-start
Adjustable test kinds, ranges, and resolutions
500V for Cat III and 300V for Cat IV
A huge, bright LCD display
AC voltage, insulation resistance, loop and line impedance, prospective earth fault current, tripping speed, and RCD/FI current are all measured.
Phase sequence signal
supported with all required accessories
self-testing feature
testing for RCD triggers, the ramp test, and continuity
Using a wiring polarity checker, broken wires are tested.
Rating for Cat III overvoltage protection up to 500V/li>
- RCD testing, ramp testing, and continuity testing
High earth voltage is detected by Earth Volt Touchpad.
Connections between Fluke Connect and FlukeCloud
DC test voltages of 50V, 100V, 250V, 500V, and 1000V for insulation
Appliances are identified using Insulation PreTest to prevent damage.
A wide variety of impressive features are included, including a strap, test leads, calibration certificate, and carry case.
Unit of light weight: 1.3 kg
AC voltage, insulation resistance, loop impedance, and line impedance (ZI) measurements
measurement of the earth resistance, tripping speed, potential earth fault current, and current generated by the RCD/FI
time-saving automatic test feature