For service engineers wishing to expand their range of services to include EV installation and maintenance, the DiLOG Advanced EV Multifunction Tester & EVSE Adaptor Kit is the best choice. This kit delivers everything you'll need to undertake a variety of safety and operational tests, ensuring installation complies with BS EN 61557. It includes both a top-of-the-line MFT and EV charge station adaptor. This system, which costs less than £1,000, offers excellent value for those wishing to enter the EV charging installation industry. While the adaptor offers compatibility with all charge stations and enables an incredible amount of safety and operational testing modes, the DL9130EV is a solid addition to their MFT range, including a variety of unique new capabilities to benefit engineers. Multifunction Tester DL9130EV:- A full EV testing sequence is included in the DL9130EV 18th Edition Multifunction Tester to confirm the DC protection offered by the EV charger as well as a 6mA pure DC test for RDC-CC verification. The Rmax and Zmax capabilities, which can automatically collect maximum values for R1+R2 continuity tests and Zs tests, respectively, and show them upon test completion, are two fresh and useful additions to this model. The DL9130EV's RGB colour display is a useful addition because it can visually represent potential pass/fail circumstances. Additionally, the screen displays values with large, legible numbers and is fully lighted, making it simple to observe in low light. The MFT supports the following RCD test types: AC, A, B, and S. For convenience, auto RCD testing is also supported. Other useful features include an auto start continuity test and auto sensing for high current 2 and 3 wire loop tests, which allow the device to recognise when users are performing 2 or 3 wire loop/PSCC measurements without the need to change modes. EVSE Adaptor for DLEV1 All MFTs and type 1/2 EV plug connectors are compatible with the DiLOG EVSE Charge Station Adaptor that is provided. In addition to having a 13A socket for MFT mains leads, this unit also has 4mm input terminals for use with 3-phase connections and can be powered through an integrated load connection. In order to guarantee appropriate functioning and connection between the charging unit and vehicle, the adaptor simulates several test modes within the charging unit, including control pilot (CP) and proximity pilot (PP). Along with Protective Earth (PE) pre-test, PE error, and error states (including CP error "E"), signal output and load connection can also all be verified.

  • Modified Data:- Size: 1360g Dimensions: 236 mm wide, 130 mm deep, and 91 mm tall. Continuity:- Display Range (0.01Ω to 2000Ω) (200mA) Range of Measurement (200mA): 0.10Ω to 2000Ω Resolutions are 0.01Ω to $19.99Ω, 20.0Ω to 199.9Ω, and 200Ω to 2000Ω. Test voltage: open circuit &gt
  • 4Vdc &gt
  • 25Vdc &gt
  • 200 mA test current Range of the display (15mA): 0.01Ω to 200Ω Accuracy: +/- 2% +/- 5 digits Resolution: 0.01Ω to 19.99Ω, 20.0Ω to 199.9Ω volts, &gt
  • 4 volts &gt
  • 25 volts open circuit, &gt
  • 15 mA IEC61557-4 and IEC61557-10 compliance Impedance of High Current Loops Accuracy (to 20Ω): +/-5% +/-12 digits -5% and +5 digits (up to 2000Ω) Range of the display: 0.01Ω to 2000Ω Range of measurement: 0.10Ω to 1999Ω (high current) Voltage supply: 195-253V, Hz: 45-65 3A RMS test current Line Impedance with High Current:- Reliability: +/-5% +/-5 digits 0.01Ω to 2000Ω in the display range 0.10Ω to 2000Ω units of measurement Resolution ranges from 0.01Ω to 9.99Ω, 10.0Ω to 99.9Ω, and 100Ω to 2000Ω. Voltage ranges: 195V to 253V and 328V to 480V 3A RMS Peak test current Insulation:- Warning: 1MΩ Screen &amp
  • Audible alarm IEC61557-2 and IEC61557-10 compliance Range of the display: 0.01Ω to 200Ω m Range of the display: 0.05Ω m to 200Ω m 5% +/- 5 digits of insulation Resolution: 0.01Ω to 1.99Ω, 2.0Ω to 19.9Ω, and 20Ω to 200Ω megapixels 250, 500, and 1000 volts for testing Specification for the test voltage: 0% to 20% (open circuit) 1mA into UN (1000/V) is the test current. Measurement of the loop test PFC:- Range of the display: 0.1A to 26.0kA Accuracy: +/-5% +/-5 digits Resolution: 0.1 A to 999.9 A, and 1 K to 2 K A PSC Measurement for a Line Test:- From 0.1 to 26.0 kA Accuracy: +/-5% +/-5 digits Resolution: 0.1 A to 999.9 A, and 1 K to 2 K A Loop Impedance with No Trip:- Voltage supply: 195-253V, Hz: 45-65 Range of the display: 0.01Ω to 2000Ω Range of measurement: 1.00Ω to 1999Ω (non-trip) Accuracy (to 20Ω): +/-5% +/-12 digits +/-5% +/-5 digits (up to 2000Ω) Resolution: 0.01 Hz to 9.99 Hz, 10.0 Hz to 99.9 Hz, and 100 Hz to 2000 Hz 15 mA RMS is the test current. Trip Time RCD Test:- Voltages: 195-253V, Hz: 45-65 Test current nominal values are 10mA/30mA/100mA (½, 1, 5, 5 I∆n), 300mA/500mA (½, 1 I∆n), and variable mode. Test for variable RCD: 1mA to 500mA Test current accuracy: -0% +10% at I∆n and 5I∆n, -0% +10% at ½ I∆n Trip time ranges include 0 to 2000ms 1/2 I∆n, 300ms to 500ms I∆n for general, and 0 to 40ms 5 I∆n for selected. Accuracy of the trip time: +/- 5% +/- 2 digits 10mA, 30mA, 100mA ( ½, 1, 5 I∆n), 300mA, and 500mA (12, 1 I∆n) are the nominal test currents. IEC 61557-6 and IEC 61557-10 compliance Trip Time Test for RDC-DD:- 195-253V, 45Hz - 65Hz 6mA -0% +10% 0 to 10000 I∆n +/- 5% +/- 2 digits 2mA - 10mA ECMI 61557-6 and ECMI 61557-10 Test for RDC (Ramp) Trip Current:- between 0.5 and 1.1 I∆n Accuracy: +/- 5% of the anticipated current Step Dimensions: 0.1* 300 milliseconds each step IEC 61557-6 and IEC 61557-10 compliance Voltage:- Range of the display: 0V to 480V Range of measurement: 0V to 480V 1V Resolution Accuracy of voltage: +/- 5% +/- 2 digits Range of frequencies: 45.0Hz to 65.0HzV precision of the frequency: +/- 1.0Hz
  • Rating for Cat III overvoltage protection up to 500V/li>
  • RCD testing, ramp testing, and continuity testing High earth voltage is detected by Earth Volt Touchpad. Connections between Fluke Connect and FlukeCloud DC test voltages of 50V, 100V, 250V, 500V, and 1000V for insulation Appliances are identified using Insulation PreTest to prevent damage. A wide variety of impressive features are included, including a strap, test leads, calibration certificate, and carry case. Unit of light weight: 1.3 kg AC voltage, insulation resistance, loop impedance, and line impedance (ZI) measurements measurement of the earth resistance, tripping speed, potential earth fault current, and current generated by the RCD/FI time-saving automatic test feature