Fluke 1625-2 GEO Earth Resistance Tester

Fluke 1625-2 GEO Earth Resistance Tester

GBP £ 2,878.56

Manufacturer: Fluke

The Fluke 1625-2 GEO Earth Resistance Tester is a distinctive and powerful product that provides an astounding assortment of testing functionalities along with a helpful array of advanced functionalities. The stakeless testing feature is the most distinctive feature of this product. The 1625-2 can measure earth ground loop resistance without the need for an earth ground stake by using just clamps fastened to an earth ground rod. This saves a significant amount of time because it eliminates the need to install and fasten stakes for every rod in your system. Additionally, the 1625 provides more standard testing features like selective earth ground rod testing, 4 pole soil resistivity testing, and 3 and 4 pole fall of potential testing. This instrument has a wide range of test capabilities in addition to some helpful additional features. The gadget can detect interferences and automatically select a measurement frequency to reduce interference impact and enhance accuracy thanks to Automatic Frequency Control (AFC). To offer a more precise reflection of earth ground resistance, the R* measuring functionality computes earth ground impedance at 55 Hz. For those seeking a feature-rich gadget with a few unique features, the Fluke 1625-2 GEO Earth Resistance Tester is an excellent option. This product is also offered in a kit form, which can be found here and includes an assortment of rods, cables, and clamps.

  • Display: 25 mm-high, 1999-digit LCD display with unique symbols Memory: Using a USB connector, internal memory may hold up to 1500 records. Measuring Procedure: Using a probe as per IEC61555-7, measure current and voltage. Frequency of measurement: 94, 105, 111, 128 Hz, either manually or automatically chosen. 55 Hz in function R* (AFC) Maximum overload: 250 V for urms Time spent measuring: 8 seconds on average with a constant frequency, 30 seconds on average with AFC, and a full cycle of all measurement frequencies 120 dB of noise rejection (162/3, 50, 60, 400 Hz) Operational temperature range: 14 °F to 122 °F (-10 °C to 50 °C). 20/48 V AC open circuit voltage The range of the RA 3-pole ground resistance measurement (IEC 1557-5) is 0.020 Ω to 19.99 kΩ, accuracy is ± (2 % rdg + 3 d), and operating error is ± (5 % rdg + 3 d). The resolution is 0.001 Ω to 10 Ω. Resolution: 0.001 Ω to 10 Ω
  • Range: 0.020 Ω to 19.99 kΩ
  • Accuracy: ± (2 % rdg + 3 d)
  • Operating Error: ± (5 % rdg + 3 d) for the RA 4-pole ground resistance measurement (IEC 1557-5) RA 3-pole current clamp selective ground resistance measurement: 0.001 Ω to 10 Ω is the resolution
  • 0.020 Ω to 19.99 kΩ is the range
  • accuracy is ± (7 % rdg + 3 d)
  • the operating error is ± (10 % rdg + 5 d). Using a current clamp, RA 4-pole selective ground resistance measurement: Precision - ± (7 % rdg + 3 d), Operating Error - ± (10 % rdg + 5 d), Resolution - 0.001 Ω to 10 Ω, Range - 0.020 Ω to 19.99 kΩ Resolution: 0.001 Ω to 10 Ω
  • Range: 0.020 Ω to 19.99 kΩ
  • Accuracy: ± (7 % rdg + 3 d)
  • Operating Error: ± (10 % rdg + 5 d) 250 milliampere-hour alternating current
  • Fall of prospective testing for poles 3 and 4 Four-pole soil resistivity measurement Automatic frequency control and R* measurement are examples of advanced functionality. Enhanced Process Shorter test periods Stakeless functional testing Particular testing