Chauvin Arnoux CA6422 Earth Tester

Chauvin Arnoux CA6422 Earth Tester

GBP £ 612.00

Manufacturer: Chauvin Arnoux

With the Chauvin Arnoux CA6422 Earth Tester, personnel may test for 2P resistance measures up to 50k and 3P earth measurements up to 2k with automatic measurement stabilisation while remaining in compliance with EC 61557-1 and IEC 61557-4 standards. The CA 6422's design places all measures and functions on the front panel, making it simple to use even with gloves on. The user interface is further improved by the illuminated LCD panel, which makes it easier to view measurement storage. The NOISE sign will flash when noise voltage is detected, while the Led will offer the operator a visual cue if dangerous voltage is present. The durable CA6422 is 600V CAT IV safety rated and complies with EC 61557-1 and IEC 61557-4 standards. The tester is protected from dust and water spray from all sides by its IP65 rating. The CA6422 has a battery life of up to 2,000 3P earth measurements at 100 when using 6 × LR6 or AA batteries.

  • Resistance 2P:- Accuracy: (2%R + 10 cts), (2%R + 2 cts), (2%R + 1 ct), etc. Range: 0.05 to 99.99, 80 to 999.9, 0.800 to 9.999, and 8 to 50 thousand 0.01 / 1 / 10 / 100 as the resolution Resistance 3P:- Accuracy: (1%R+10 cts), (1%R+2 cts), or (1%R+1 ct) Frequency of measurement: 128 Hz or 256 Hz One-shot vs. ongoing measurement voltage with no load: 10 V peak Range: 0.5Ω - 2,000Ω Resolutions of 0.01, 0.1, and 1 General specifications:- Battery life: more than 2,000 times at 100 x 3P earth measurements. IEC 61557-1 and IEC 61557-5 are in compliance with IEC 61557. Drop test: 1 m in accordance with IEC 61010-1 1 kilogramme and 223 x 126 x 70 mm in size. Display: Custom backlit 206 segment LCD Environment: -10 to +50°C for operation and -40 to +70°C for storage (without batteries or accumulators) IK 04 according to IEC 50102 and IP 65 in accordance with IEC 60529 Measurement Modes: R 2P and R 3P Protection: Any input terminals up to 600 V 6 LR-6 or AA batteries for power/li&gt
  • Electrical safety standards include IEC 61326-1 for EMC and IEC 61010-2-030 for 600 V CAT IV.
  • IEC 61010-1 1 metre drop test Resistance for 2P: 0.05 to 50 k Earth 3P: 0.5 to 2k Rated at 600V CAT IV Battery life is greater than 2,000 times 3P earth measurements at 100. Meets IEC 61557-1 and IEC 61557-4 requirements. Rated IP65 Measurement approaches: one-time or ongoing Power source 6 LR6, AA, or C batteries