The Chauvin Arnoux CA6536 Insulation Tester is ideal for specialized industries like aerospace, defense, and aviation where insulation needs to be tested at particular low voltages because of its fully adjustable test voltage, which ranges from 10V to 100V. With the test voltage, accuracy is only ±0.5V. The tester is capable of accurately testing various types of insulation, with a measurement range of 2kΩ to 20GΩ. It also has useful extra features like continuity and regular resistance testing. With this megohmmeter, AC voltage up to 700V can also be measured. The Chauvin Arnoux CA6536 is incredibly versatile, with timed, programmable insulation testing and adjustable alarms. Its straightforward interface also makes operation a breeze. A backlit digital screen featuring an analog bar graph shows the results, and the tester also includes a relative mode for comparing various results. The tester is simple to use hands-free thanks to the magnetic mount and standard remote control probe with torch. It comes with a two-year warranty and is rated as Cat IV 600V. Test leads, a crocodile clip, a carry case, and wire grips are among the additional accessories that are provided.
- Voltage
Resolution / Measurement range: 0.3 V to 399.9 V / 0,1 V
- 400 V to 700 V / 1 V
Accuracy / Input impedance: 400 kΩ / ± (3 % + 2 cts)
15.3–800 Hz is the DC operating frequency.
Insulation
Test voltage: 1 V increments from 10 to 100 V
Maximum test voltage range: 20 GΩ
Respect for the IEC 61557-2 standard: Two G
Measurement range: 2kΩ - 1GΩ at 10V
Range of measurement at 25 volts: (UN/5) kΩ - (UN/5) GΩ
The measurement range is (UN/5) kΩ - (UN/5) GΩ at 50V.
20 kΩ–20 GΩ is the measurement range at 100V.
Test voltage variation: 10V to 100V
10(1)-999 kΩ and 1.000-3.999 MΩ / 1 kΩ
- 4.00 - 39.99 MΩ / 10 kΩ
- 40.0-399.9 MΩ / 100 kΩ
- 400 - 3,999 MΩ / 1 MΩ
- 4.00 - 39.99 GΩ / 10 MΩ
- 40.0 - 200 GΩ / 100 MΩ are the measurement range and resolution.
Precision: ± (3% + 2 cts)
Test voltage: ±0.5V (I <
- 1 mA)
Test voltage display: ± (3 % + 3 cts)
Test current/resolution display: 0.01 µA-19.99 µA / 10 nA
- 40.0 -399.9 µA / 100 nA
- 0.400
Continuity
The continuity measurement range is as follows: 0.0 – 100.0 Ω (20 mA)
- 0.00 Ω–10.00 Ω (200 mA).
Precision / Voltage of the open circuit: ± (2 % + 2 cts) / ≥ 6 V
Current used for measurement: 20 mA range: 20 mA ± 5 mA
- 200 mA range: 200 mA (-0 mA + 20 mA).
Continuity thresholds (2 Ω, 1 Ω, programmable threshold) for the rapid beep
Cable compensation: up to 9.99 Ω
Resistance
0 -3,999 Ω / 1 Ω
- 4.00 kΩ - 39.99 kΩ / 10 Ω / ± (3 % + 2 cts)
- 40.0 kΩ - 399.9 kΩ / 100 Ω
- 400 kΩ-1,000 kΩ / 1 kΩ / ± (3 % + 2 cts)
General specifications
Display: logarithmic bargraph plus two x 4,000 cts
Power supply/autonomous shutdown: six LR6 (AA) batteries /deactivatable, five minutes
Measurements: UN x 1 kΩ @ UN (5 s ON / 55 s OFF)
- 3,000 continuity measurements (5 s ON / 55 s OFF)
- battery life: 1,500/2,500/6,000
Dimensions: 211 x 108 x 60 mm / 850 g / IP 54 / IK 04
- weight
- dimensions (h x w x d)
-
IEC 61326-1, IEC 61010-1, and IEC 61010-2-030, 600 V CAT IV, EMC and electrical safety
Standards compliance: IEC 61557 parts 1, 2, 4, and 10
Two-year warranty
- Variable test voltage range of 10 to 100 volts
Ideal for extremely specialized testing
Tests for resistance and continuity
AC voltage measurement up to 700V and insulation resistance up to 20GΩ
Timed insulation tests that can be programmed
Fixed and movable alarms
Mode of relative measurement
Cat IV 600V remote control probe with torch
Two-year guarantee