Kewtech KT63DL Multifunction 5 in 1 Tester

Kewtech KT63DL Multifunction 5 in 1 Tester

GBP £ 830.09

Manufacturer: Kewtech

The Kewtech KT63DL Multifunction 5 in 1 Tester is suitable for testing and certifying both household and commercial electrical installations since it crams a lot of functionality into a straightforward, user-friendly design. With an auto discharge feature, the device can test insulation up to 1000V, range continuity measures up to 2000, and fully test all RCD types with no trip loops.There are no bangs during testing, including during the auto test for RCDs up to 30mA, thanks to the simultaneous display of PSC/PFC data, loop impedance, and innovative anti-trip loop testing technology. These outcomes include a low vulnerability to RCD uplift and noise interference, and a ramp test feature is also integrated for optimal reliability. The KT63DL can perform mains polarity tests, can auto-null test leads for continuity, and is completely protected against phase to phase connection. Along with increasing the instrument's efficiency, a built-in instant correct wiring status check and independent hands-free mode controlled by a separate button also increase the operator's safety. With a tactile interface made out of easy-press buttons and a single rotary dial for function selection, the IP65 rated housing is portable and ergonomic. The KT63DL comes with an end of line calibration certificate, an ACC063 3 wire distribution board test lead and a soft carrying box.

  • measurement of AC voltage:- Range:500 volts 1V as the resolution Accuracy from 45 to 66 Hz: 0.8% + 3 counts 360kΩ input impedance 660V rms overload protection RLO continuity testing Range (autoranging): 20 cents, 200 cents, and 2000 cents Resolutions of 0.01Ω, 0.1Ω, and 1Ω Voltage of an open circuit: &gt
  • 4V General:- Size: 10 x 25 x 12.5 cm (L x W x H). Weight (batteries included): 1.3 kg IP-40 Sealing Cat III to 500V
  • Cat IV to 300V of excess voltage Safety: Meets with the demands of EN61010-1 Ed 2.0 (2001-02), UL61010, ANSI/ISA -s82.02.01 2000, and CAN/CSA c22.2 No. 1010 2nd edition. Performance: Second Editions of EN61557-1 to EN61557-7 and EN61557-10 6 x AA batteries measuring insulation resistance:- Test voltages: 50, 100, 250, 500, and 1000V tTest voltage accuracy (at the specified test current): +10%, -0% Ranges of insulation resistance: 20 to 50 MΩ, 20 to 100 MΩ, 20 to 200 MΩ, 20 to 200 MΩ, and 20 to 200 MΩ. Resolution: 0.01MΩ / 0.1MΩ
  • 0.01MΩ / 0.1MΩ
  • 0.01MΩ / 0.1MΩ
  • 0.01MΩ / 0.1MΩ / 1MΩ
  • 0.01MΩ / 0.1MΩ / 1MΩ Test currents of 1mA at 50kΩ
  • 1mA at 100kΩ
  • 1mA at 250kΩ
  • 1mA at 500kΩ
  • 1mA at 1MΩ Impedance of loops and lines (ZI):- High current mΩ mode
  • range: 10Ω
  • 0.001Ω
  • Resolutions of 0.01Ω, 0.1Ω, and 1Ω PSC test for prospective earth fault current:- 1000A to 10kA (50kA) range 1A/0.1kA resolution By dividing the actual mains voltage by the measured loop (L-PE) resistance or line (L-N) resistance, respectively, prospective earth fault current (PEFC) or prospective short current (PSC) are determined. RCD testing and varieties of RCD testing:- Type of RCD: A4, AC1, G2, S3 Notes: (1) Reacted to AC, (2) In general no delay, (3) Time delay, and (4) Reacted to pulsed signal Measurement of RCD/FI-Tripping Current and Ramp Testing (IΔN):- 30% to 110% of the RCD-rated current is the current range. 10% of IΔN2 as a step size Dwell time: Type G: 300 ms
  • Type S: 500 ms ±5%5% accuracy in measurements Trip current ranges that have been specified (EN 61008-1) are as follows: 50% to 100% for Type AC, 35% to 140% for Type A (&gt
  • 10 mA), 35% to 200% for Type A (≤10 mA), 50% to 200% for Type B, and ²5% for Type B. Notes: For Type A IΔN &gt
  • 10 mA, ¹30% to 150%
  • for Type A IΔN = 10 mA, 30% to 210%
  • for Type B, 20% to 210%. Testing the tripping speed (T):- Current settings1: 10-30-100-300-500-1000mA - VAR
  • 10-30-100mA A multiplier of 0.5, 1, and 5 Measurement of AC voltage:- Range:500 volts 1V as the resolution Accuracy from 45 to 66 Hz: 0.8% + 3 counts 360kΩ input impedance 660V rms overload protection RLO continuity testing Range (autoranging): 20 cents, 200 cents, and 2000 cents Resolutions of 0.01Ω, 0.1Ω, and 1Ω Voltage of an open circuit: &gt
  • 4V Test for Earth Resistance (RE) Range: 200Ω / 2000Ω 0.1 / 1 resolution the frequency 128 Hz. Voltage at output: 25V Connect Fluke:- Operating systems iOS 8 and later or Android 4.4 and later support Fluke Connect. General:- Size: 10 x 25 x 12.5 cm (L x W x H). Weight (batteries included): 1.3 kg IP-40 Sealing Cat III to 500V
  • Cat IV to 300V of excess voltage Safety: Meets with the demands of EN61010-1 Ed 2.0 (2001-02), UL61010, ANSI/ISA -s82.02.01 2000, and CAN/CSA c22.2 No. 1010 2nd edition. Performance: Second Editions of EN61557-1 to EN61557-7 and EN61557-10 6 x AA batteries Measuring insulation resistance:- Test voltages: 50, 100, 250, 500, and 1000V tTest voltage accuracy (at the specified test current): +10%, -0% Ranges of insulation resistance: 20 to 50 MΩ, 20 to 100 MΩ, 20 to 200 MΩ, 20 to 200 MΩ, and 20 to 200 MΩ. Resolution: 0.01MΩ / 0.1MΩ
  • 0.01MΩ / 0.1MΩ
  • 0.01MΩ / 0.1MΩ
  • 0.01MΩ / 0.1MΩ / 1MΩ
  • 0.01MΩ / 0.1MΩ / 1MΩ Test currents of 1mA at 50kΩ
  • 1mA at 100kΩ
  • 1mA at 250kΩ
  • 1mA at 500kΩ
  • 1mA at 1MΩ Impedance of loops and lines (ZI):- High current mΩ mode
  • range: 10Ω
  • 0.001Ω
  • Resolutions of 0.01Ω, 0.1Ω, and 1Ω PSC test for prospective earth fault current:- 1000A to 10kA (50kA) range 1A/0.1kA resolution By dividing the actual mains voltage by the measured loop (L-PE) resistance or line (L-N) resistance, respectively, prospective earth fault current (PEFC) or prospective short current (PSC) are determined. RCD testing and varieties of RCD testing:- RCD type: G2, S3, AC1, Model 1664: A, AC, B5, S Notes: (1) Reacted to AC, (2) In general no delay, (3) Time delay, and (4) Reacted to pulsed signal
  • (5) Responds to smooth DC signal. Measurement of RCD/FI-Tripping Current and Ramp Testing (IΔN):- 30% to 110% of the RCD-rated current is the current range. 10% of IΔN2 as a step size Dwell time: Type G: 300 ms
  • Type S: 500 ms ±5%5% accuracy in measurements Trip current ranges that have been specified (EN 61008-1) are as follows: 50% to 100% for Type AC, 35% to 140% for Type A (&gt
  • 10 mA), 35% to 200% for Type A (≤10 mA), 50% to 200% for Type B, and ²5% for Type B. Notes: For Type A IΔN &gt
  • 10 mA, ¹30% to 150%
  • for Type A IΔN = 10 mA, 30% to 210%
  • for Type B, 20% to 210%. Testing the tripping speed (T):- Current settings1: 10-30-100-300-500-1000mA - VAR
  • 10-30-100mA A multiplier of 0.5, 1, and 5 Specifications for the Fluke 1663 Multifunction Tester Measurement of AC voltage:- 500 volts Range 1V as the resolution Precision from 45 to 66 Hz: 0.8% plus 3 counts 360 k input impedance 660V rms overload protection RLO continuity testing:- Range: 20 cents, 200 cents, and 2000 cents Resolutions of 0.01, 0.1, and 1 Voltage of an open circuit: &gt
  • 4V Test for Earth Resistance (RE):- Range: 200Ω / 2000Ω 0.1 / 1 resolution the frequency 128 Hz. General:- Size: 10 x 25 x 12.5 cm (L x W x H). Batteries: 6 x AA Weight (with batteries): 1.3 kg IP-40 Sealing Safety: Complies with EN61010-1 Ed 2.0 (2001-02), UL61010, ANSI/ISA -s82.02.01 2000, and CAN/CSA c22.2 No. 1010 second edition regulations. Cat III to 500V
  • Cat IV to 300V of excess voltage Performance: Second Editions of EN61557-1 through EN61557-7 and EN61557-10 Measuring Insulation Resistance:- Test voltages: 50, 100, 250, 500, and 1000V Test voltage accuracy (at the specified test current): +10%, -0% Test voltage: 50, 100, 250, 500, and 1000 volts. Ranges of insulation resistance: 20 to 50 M, 20 to 100 M, 20 to 200 M, 20 to 200 M, and 20 to 200 M. Resolution: 0.01M/0.1M, 0.01M/0.1M, 0.01M/0.1M, 0.01M/0.1M/1M, and 0.01M/0.1M/1M Test currents of 1 mA at 50 k, 100 k, 250 k, 500 k, and 1 mA at 1 m Impedance of loops and lines (ZI):- High current mΩ mode
  • range: 10
  • 0.001
  • Resolution of 0.01, 0.1, and 1 RCD testing and kinds of RCD testing:- RCD type: G2, S3, AC1, Model 1663: G2, S3, A4, AC1, Reactions to AC, general no delay, time delay, and pulsed signal are noted. Measurement of RCD/FI-Tripping Current and Ramp Testing (I-N):- 30% to 110% of the RCD-rated current is the current range. 10% of IN2 as a step size Dwell time: Type G: 300 ms
  • Type S: 500 ms Measurement precision: 5% Trip current ranges that have been specified (EN 61008-1) are as follows: 50% to 100% for Type AC, 35% to 140% for Type A (&gt
  • 10 mA), 35% to 200% for Type A (10 mA), 50% to 200% for Type B, and 25% for Type B. Notes: For Type A IN &gt
  • 10 mA, 130% to 150%
  • for Type A IN = 10 mA, 30% to 210%
  • for Type B, 20% to 210%. Test of tripping speed (T):- Settings as of right now1: 10-30-100-300-500-1000mA - VAR
  • 10-30-100mA A multiplier of 0.5, 1, and 5 Range of measurements: 510ms, 160ms (RCD Type)
  • 310ms, 50ms (RCD Type G). Measurement of AC voltage:- Range:500 volts 1V as the resolution Accuracy from 45 to 66 Hz: 0.8% + 3 counts 360kΩ input impedance 660V rms overload protection RLO continuity testing Range (autoranging): 20 cents, 200 cents, and 2000 cents Resolutions of 0.01Ω, 0.1Ω, and 1Ω Voltage of an open circuit: &gt
  • 4V Test for Earth Resistance (RE) Range: 200Ω / 2000Ω 0.1 / 1 resolution the frequency 128 Hz. Voltage at output: 25V Connect Fluke:- Operating systems iOS 8 and later or Android 4.4 and later support Fluke Connect. General:- Size: 10 x 25 x 12.5 cm (L x W x H). Weight (batteries included): 1.3 kg IP-40 Sealing Cat III to 500V
  • Cat IV to 300V of excess voltage Safety: Meets with the demands of EN61010-1 Ed 2.0 (2001-02), UL61010, ANSI/ISA -s82.02.01 2000, and CAN/CSA c22.2 No. 1010 2nd edition. Performance: Second Editions of EN61557-1 to EN61557-7 and EN61557-10 6 x AA batteries Measuring insulation resistance:- Test voltages: 50, 100, 250, 500, and 1000V tTest voltage accuracy (at the specified test current): +10%, -0% Ranges of insulation resistance: 20 to 50 MΩ, 20 to 100 MΩ, 20 to 200 MΩ, 20 to 200 MΩ, and 20 to 200 MΩ. Resolution: 0.01MΩ / 0.1MΩ
  • 0.01MΩ / 0.1MΩ
  • 0.01MΩ / 0.1MΩ
  • 0.01MΩ / 0.1MΩ / 1MΩ
  • 0.01MΩ / 0.1MΩ / 1MΩ Test currents of 1mA at 50kΩ
  • 1mA at 100kΩ
  • 1mA at 250kΩ
  • 1mA at 500kΩ
  • 1mA at 1MΩ Impedance of loops and lines (ZI):- High current mΩ mode
  • range: 10Ω
  • 0.001Ω
  • Resolutions of 0.01Ω, 0.1Ω, and 1Ω PSC test for prospective earth fault current:- 1000A to 10kA (50kA) range 1A/0.1kA resolution By dividing the actual mains voltage by the measured loop (L-PE) resistance or line (L-N) resistance, respectively, prospective earth fault current (PEFC) or prospective short current (PSC) are determined. RCD testing and varieties of RCD testing:- RCD type: G2, S3, AC1, Model 1664: A, AC, B5, S Notes: (1) Reacted to AC, (2) In general no delay, (3) Time delay, and (4) Reacted to pulsed signal
  • (5) Responds to smooth DC signal. Measurement of RCD/FI-Tripping Current and Ramp Testing (IΔN):- 30% to 110% of the RCD-rated current is the current range. 10% of IΔN2 as a step size Dwell time: Type G: 300 ms
  • Type S: 500 ms ±5%5% accuracy in measurements Trip current ranges that have been specified (EN 61008-1) are as follows: 50% to 100% for Type AC, 35% to 140% for Type A (&gt
  • 10 mA), 35% to 200% for Type A (≤10 mA), 50% to 200% for Type B, and ²5% for Type B. Notes: For Type A IΔN &gt
  • 10 mA, ¹30% to 150%
  • for Type A IΔN = 10 mA, 30% to 210%
  • for Type B, 20% to 210%. Testing the tripping speed (T):- Current settings1: 10-30-100-300-500-1000mA - VAR
  • 10-30-100mA A multiplier of 0.5, 1, and 5 Specifications for the Fluke 1663 Multifunction Tester Measurement of AC voltage:- 500 volts Range 1V as the resolution Precision from 45 to 66 Hz: 0.8% plus 3 counts 360 k input impedance 660V rms overload protection RLO continuity testing:- Range: 20 cents, 200 cents, and 2000 cents Resolutions of 0.01, 0.1, and 1 Voltage of an open circuit: &gt
  • 4V Test for Earth Resistance (RE):- Range: 200Ω / 2000Ω 0.1 / 1 resolution the frequency 128 Hz. General:- Size: 10 x 25 x 12.5 cm (L x W x H). Batteries: 6 x AA Weight (with batteries): 1.3 kg IP-40 Sealing Safety: Complies with EN61010-1 Ed 2.0 (2001-02), UL61010, ANSI/ISA -s82.02.01 2000, and CAN/CSA c22.2 No. 1010 second edition regulations. Cat III to 500V
  • Cat IV to 300V of excess voltage Performance: Second Editions of EN61557-1 through EN61557-7 and EN61557-10 Measuring Insulation Resistance:- Test voltages: 50, 100, 250, 500, and 1000V Test voltage accuracy (at the specified test current): +10%, -0% Test voltage: 50, 100, 250, 500, and 1000 volts. Ranges of insulation resistance: 20 to 50 M, 20 to 100 M, 20 to 200 M, 20 to 200 M, and 20 to 200 M. Resolution: 0.01M/0.1M, 0.01M/0.1M, 0.01M/0.1M, 0.01M/0.1M/1M, and 0.01M/0.1M/1M Test currents of 1 mA at 50 k, 100 k, 250 k, 500 k, and 1 mA at 1 m Impedance of loops and lines (ZI):- High current mΩ mode
  • range: 10
  • 0.001
  • Resolution of 0.01, 0.1, and 1 RCD testing and kinds of RCD testing:- RCD type: G2, S3, AC1, Model 1663: G2, S3, A4, AC1, Reactions to AC, general no delay, time delay, and pulsed signal are noted. Measurement of RCD/FI-Tripping Current and Ramp Testing (I-N):- 30% to 110% of the RCD-rated current is the current range. 10% of IN2 as a step size Dwell time: Type G: 300 ms
  • Type S: 500 ms Measurement precision: 5% Trip current ranges that have been specified (EN 61008-1) are as follows: 50% to 100% for Type AC, 35% to 140% for Type A (&gt
  • 10 mA), 35% to 200% for Type A (10 mA), 50% to 200% for Type B, and 25% for Type B. Notes: For Type A IN &gt
  • 10 mA, 130% to 150%
  • for Type A IN = 10 mA, 30% to 210%
  • for Type B, 20% to 210%. Test of tripping speed (T):- Settings as of right now1: 10-30-100-300-500-1000mA - VAR
  • 10-30-100mA A multiplier of 0.5, 1, and 5 Range of measurements: 510ms, 160ms (RCD Type)
  • 310ms, 50ms (RCD Type G). Measurement of AC voltage:- 500 volts 0.1V as the resolution Accuracy from 45 to 66 Hz: 0.8% plus 3 counts 360 k input impedance 660V rms overload protection Test for Earth Resistance (RE):- the frequency is128 Hz. Range: 200Ω / 2000Ω 0.1 / 1 resolution Voltage at output: 25V Connect Fluke:- Operating systems iOS 8 and later or Android 4.4 and later support Fluke Connect. General:- AA x 6 batteries, Cat III to 500V
  • Cat IV to 300V of excess voltage Performance: Second Editions of EN61557-1 through EN61557-7 and EN61557-10 Size: 10 x 25 x 12.5 cm (L x W x H). IP-40 Sealing Safety: Complies with EN61010-1 Ed 2.0 (2001-02), UL61010, ANSI/ISA -s82.02.01 2000, and CAN/CSA c22.2 No. 1010 second edition regulations. Weight (batteries included): 1.3 kg Measuring Insulation Resistance:- Test voltage accuracy (at the specified test current): +10%, -0% Ranges of insulation resistance: 20 to 50 M, 20 to 100 M, 20 to 200 M, 20 to 200 M, and 20 to 200 M. Resolution: 0.01M/0.1M, 0.01M/0.1M, 0.01M/0.1M, 0.01M/0.1M/1M, and 0.01M/0.1M/1M Test voltages: 50, 100, 250, 500, and 1000V Test voltage: 50, 100, 250, 500, and 1000 volts. Test currents of 1 mA at 50 k, 100 k, 250 k, 500 k, and 1 mA at 1 m Impedance of Loops and Lines (ZI):- High current m mode
  • range: 10
  • 0.001
  • Resolutions of 0.01, 0.1, and 1 PSC Test for Prospective Earth Fault Current:- 1000A to 10kA (50kA) range 1A/0.1kA resolution Calculation: To determine the prospective earth fault current (PEFC) or prospective short current (PSC), divide the measured loop resistance (L-PE) or line resistance (L-N) by the actual mains voltage, accordingly. RCD Testing and Kinds of RCD Testing:- Model 1664: A, AC, B5, S RCD type: AC1
  • G2, S3. Notes: For Type A IN &gt
  • 10 mA, 130% to 150%
  • for Type A IN = 10 mA, 30% to 210%
  • for Type B, 20% to 210%. Measurement of RCD/FI-Tripping Current and Ramp Testing (IΔN):- 30% to 110% of the RCD rated current is the current range.1 10% of IN2 as a step size Dwell time: Type G: 300 ms
  • Type S: 500 ms Measurement precision: 5% Trip current ranges that have been specified (EN 61008-1) are as follows: 50% to 100% for Type AC, 35% to 140% for Type A (&gt
  • 10 mA), 35% to 200% for Type A (10 mA), 50% to 200% for Type B, and 25% for Type B. Reactions to AC, general no delay, time delay, pulsed signal, and smooth DC signal are noted. Test of tripping speed (ΔT):- Settings as of right now1: 10-30-100-300-500-1000mA - VAR
  • 10-30-100mA A multiplier of 0.5, 1, and 5 Range of measurements: 510ms, 160ms (RCD Type)
  • 310ms, 50ms (RCD Type G). KT63DL:* :- Test for 200mA Continuity Insulation Resistance at 250, 500, and 1000V Test of a three-wire no-trip loop A screen that displays all Auto RCD results Test Lead Automatic Null The backlight Permanent Live Warning LED High Voltage Light Test of the High Current Loop &#039
  • Hands Free&#039
  • Testing IP Score: 54 PAT Testing using PAT Adaptor 1, optional Test PSC/PFC 10, 30, 100, 300, and 500 mA for RCD Type AC &amp
  • A RCD Type ACS and A: 100 and 300 mA ACS, ACS, &amp
  • AS 10, 30, 100, 300, 500, &amp
  • 1000 mA RCD Type AC 30 mA RCD Auto Test soft carrying case Voltage Measurement - Checking the wiring and lead polarity *KT63 Plus:* :- Test for 200mA Continuity Insulation Resistance at 250, 500, and 1000V Test of a three-wire no-trip loop A screen that displays all Auto RCD results Test Lead Automatic Null The backlight Permanent Live Warning LED High Voltage Light Test of the High Current Loop &#039
  • Hands Free&#039
  • Testing IP Score: 54 PAT Testing using PAT Adaptor 1, optional Test PSC/PFC 10, 30, 100, 300, and 500 mA for RCD Type AC &amp
  • A RCD Type ACS and A: 100 and 300 mA ACS, ACS, &amp
  • AS 10, 30, 100, 300, 500, &amp
  • 1000 mA RCD Type AC 30 mA RCD Auto Test soft carrying case Voltage Measurement Checking the wiring and lead polarity *KT65DL:*:- Test for 200mA Continuity Insulation Resistance at 250, 500, and 1000V Test of a three-wire no-trip loop Test Lead Automatic Null Permanent Live Warning LED High Voltage Light Test of the High Current Loop PAT Testing using PAT Adaptor 1, optional Test PSC/PFC 10, 30, 100, 300, and 500 mA for RCD Type AC &amp
  • A A screen that displays all Auto RCD results: The backlight: &#039
  • Hands Free&#039
  • Testing IP Score: 40 100 and 300 mA for RCD Type ACS &amp
  • A: RCD Auto Test: 30 mA
  • RCD Type AC: ACS, ACS &amp
  • AS 10, 30, 100, 300, 500 &amp
  • 1000 mA
  • 10, 30, 100, 300, 500, &amp
  • 1000 mA RCD Auto Test: Soft carrying case Checking the wiring and lead polarity: Voltage Measurement *KT66DL:*:- - Test for a two-wire no-trip loop Test of the High Current Loop RCD Auto Test Results All Shown On One Screen Test the 6mA DC RCD (for EVSE) Loop Test at 55V Rotation of the phase Instrument Protective Lid Earth Potential Limits Touch Pad (25V or 50V) Test Lockout Button Test for Earth Resistance Hardware for PAT Tests Downloading Memory Colour Display 25A Test Current with 50kA PFC Range Test Current Continuity 15 mA Option Insulation at 100 volts Dielectric Absorption Index and Polarisation Bargraph of digital insulation resistance
  • Automatic loop evaluation is made possible by built-in loop impedance tables. An excellent choice for testing TT and TN systems Circuit testing time is decreased by automated RCD testing Loop evaluation is automated by the built-in loop impedance tables. suitable for testing single- and three-phase installation Schematic assistance displays for on-site use and convenience real-time monitoring of all three voltages rechargeable batteries built-in with the charger Reversing polarity automatically during a continuity test Trip Lock to stop tripping of RCDs and RCBOs upgradeable to conform to any changes in wiring requirements Calculates projected short (PSC/IK) and prospective earth fault current (PEFC/IK). Contains Z-max memory for loop tests so you can quickly determine the highest loop test value. loop and line resistance, as well as insulation resistance, are measured. Test the continuity of the motor windings. Test the ramp by measuring the RCD switching time and tripping level. Trip time and current for RCD type A and AC are measured in one test. RCD variable current is measured. gives access to a special zero adaptor for quick, precise, and reliable test lead and main cord compensation. provides an RCD test cycle that is automatic. Phase-sequence signal RCD testing, ramp testing, and continuity testing 500V for Cat III and 300V for Cat IV Security rankings Ground Volt Touchpad recognises elevated earth voltage Smartphone connectivity for Fluke Connect and FlukeCloud Insulation PreTest recognises appliances to prevent harm. DC test voltages of 50V, 100V, 250V, 500V, and 1000V for insulation AC voltage, insulation resistance, loop impedance, and line impedance (ZI) measurements measurement of the earth resistance, tripping speed, potential earth fault current, and current generated by the RCD/FI includes all required add-ons, such as a remote probe and an FTP fused test probe set. time-saving automatic test feature strong construction and lightweight portability